Flexible Sprinkler Drops(for Clean Room)
CLEAN ROOM TYPE
Quick and easy to assemble for commercial use, not a cleaner dedicated reducer
- Stainless Steel 304
- Zinc-plated Steel (Nut & Nipple)
- EPDM Sealing Gasket
- Nylon Isolating Ring
- KFI Approved
Flexible Sprinkler drops for Clean room
The clean room is designed to maintain the cleanliness of the suspended particles in the air below the specified value in the specified particle size, to maintain the cleanliness specified in the supply utility for the materials, chemicals, / Pressure / Air flow / Noise / Vibration. Recent trends in cleanroom management have shifted from micro-particle management to nanometer-scale noxious gas management
Available in offices, hospitals, pharmaceutical companies, chemical plants, etc.
- It is a welding type of general type. And you can use it in a normal office that requires a semi- clean room type
Customizable style
- It can be made with SGP in the form of both nuts, one-piece nuts and welded nipples.
Patented one-touch bracket
- Made with know-how of Daejin industry accumulated over 30 years
Automatic Sprinkler Systems / Flexible Sprinkler Hose with Fittings / for Commercial Suspended Ceilings
NPT / BSPT in. | k-Factor | Minimum Bend Radius in. (mm) |
Number of Bends |
Rated Working Pressure psi (kPa) |
Hose Assembly length in (mm) |
Equivalent Length of 1 in. Schedule 40 Pipe, ft (m) |
---|---|---|---|---|---|---|
1/2 | 5.6 | 8 (203) | 1 | 175 (1205) | 24 (610) | 8.8 (2.2) |
1/2 | 5.6 | 8 (203) | 2 | 175 (1205) | 31.2 (792) | 14(4.3) |
1/2 | 5.6 | 8 (203) | 2 | 175 (1205) | 36 (915) | 17.5 (5.3) |
1/2 | 5.6 | 8 (203) | 3 | 175 (1205) | 48 (1220) | 26.3 (8) |
1/2 | 5.6 | 8 (203) | 4 | 175 (1205) | 60 (1525) | 31.4 (9.5) |
1/2 | 5.6 | 8 (203) | 4 | 175 (1205) | 72 (1830) | 36.6 (11.1) |
CLEAN ROOM TYPE
Most popular models that can be used with ordinary sprinklers
- Stainless Steel 304
- Zinc-plated Steel (Nut & Nipple)
- EPDM Sealing Gasket
- Nylon Isolating Ring
- KFI Approved
Flexible Sprinkler drops for Clean room
The clean room is designed to maintain the cleanliness of the suspended particles in the air below the specified value in the specified particle size, to maintain the cleanliness specified in the supply utility for the materials, chemicals, / Pressure / Air flow / Noise / Vibration. Recent trends in cleanroom management have shifted from micro-particle management to nanometer-scale noxious gas management
Most commonly used in cleanrooms
- General product with reducer and nipple welded on both ends of flexible tube
Completely block external air
- Connecting to the grid when installing the clean room ceiling panel, the reducer is inserted into the center of the cross, fixed with both fixing brackets, and the outside air is blocked through the O-ring
The connection of the nipple is field welding type and assembly type using sleeve nuts.
Automatic Sprinkler Systems / Flexible Sprinkler Hose with Fittings / for Clean Room Ceilings
NPT / BSPT in. | k-Factor | Minimum Bend Radius in. (mm) |
Number of Bends |
Rated Working Pressure psi (kPa) |
Hose Assembly length in (mm) |
Equivalent Length of 1 in. Schedule 40 Pipe, ft (m) |
---|---|---|---|---|---|---|
1/2 | 5.6 | 8 (203) | 1 | 175 (1205) | 24 (610) | 11.9 (3.6) |
1/2 | 5.6 | 8 (203) | 2 | 175 (1205) | 31.2 (792) | 14.7 (4.5) |
1/2 | 5.6 | 8 (203) | 2 | 175 (1205) | 36 (915) | 16.5 (5) |
1/2 | 5.6 | 8 (203) | 3 | 175 (1205) | 48 (1220) | 21.2 (6.5) |
1/2 | 5.6 | 8 (203) | 4 | 175 (1205) | 60 (1525) | 27.3 (8.3) |
1/2 | 5.6 | 8 (203) | 4 | 175 (1205) | 72 (1830) | 33.4 (10.1) |
CLEAN ROOM TYPE
Use in clean rooms of semiconductor factories such as PDP, TFT, LCD that is available with a regular sprinklers
- Stainless Steel 304
- Zinc-plated Steel (Nut & Nipple)
- EPDM Sealing Gasket
- Nylon Isolating Ring
- KFI Approved
Flexible Sprinkler drops for Clean room
The clean room is designed to maintain the cleanliness of the suspended particles in the air below the specified value in the specified particle size, to maintain the cleanliness specified in the supply utility for the materials, chemicals, / Pressure / Air flow / Noise / Vibration. Recent trends in cleanroom management have shifted from micro-particle management to nanometer-scale noxious gas management
SGP Panel Type - New Type
- Panel thickness is available from 15T to 150T Installation is easier than the old type and saves time After installation, it looks good. Sleeve nut type and weld type are manufactured by user order
SGP Panel Type - Old Type
- Panel thickness is available from 15T to 150T Easy to install, Sleeve nut type and weld type are manufactured by user order
Automatic Sprinkler Systems / Flexible Sprinkler Hose with Fittings / for Clean Room Ceilings
NPT / BSPT in. | k-Factor | Minimum Bend Radius in. (mm) |
Number of Bends |
Rated Working Pressure psi (kPa) |
Hose Assembly length in (mm) |
Equivalent Length of 1 in. Schedule 40 Pipe, ft (m) |
---|---|---|---|---|---|---|
1/2 | 5.6 | 8 (203) | 1 | 175 (1205) | 24 (610) | 11.9 (3.6) |
1/2 | 5.6 | 8 (203) | 2 | 175 (1205) | 31.2 (792) | 14.7 (4.5) |
1/2 | 5.6 | 8 (203) | 2 | 175 (1205) | 36 (915) | 16.5 (5) |
1/2 | 5.6 | 8 (203) | 3 | 175 (1205) | 48 (1220) | 21.2 (6.5) |
1/2 | 5.6 | 8 (203) | 4 | 175 (1205) | 60 (1525) | 27.3 (8.3) |
1/2 | 5.6 | 8 (203) | 4 | 175 (1205) | 72 (1830) | 33.4 (10.1) |